MULTI-CHANNEL PROTECTION AND PREDICTIVE MAINTENANCE SYSTEM
The MOVISYS system is designed for the real-time multi-channel protection of machines. It consists of a 19, 6U industrial rack.
Its modular structure allows for the connection of up to 52 transducers for real-time monitoring.
MOVISYS is compliant with the main specifications of standards API 670 and 678, ISO 2954 and 7919.
In addition to its protection function, MOVISYS can be coupled to a trending platform or a predictive maintenance platform.
General characteristics
Presentation & capacity
- 19'' x 6 U rack
- Number of slots per racks: 13
- 4-channel protection module = 1 slot
- Maximum number of real-time channels per rack: 52 channels
- Module 4-channel bargraph visual display module = 3 slots
Global functions
- Monitoring inhibition: 1 logical input per rack
- Alarm acknowledgement: 1 logical input per rack
- Trip multiply: 1 logical input per rack
- General power supply: 115/230V ac (optional 24Vdc or 48Vdc)
Safety
- Each module has its own regulated power supply, so that a defective module does not affect the operating of the other modules.
- Permanent monitoring of the bias voltages
- Permanent monitoring of signal saturation
- Permanent monitoring of power supplies
- Internal self-tests: RAM, memory, PROM, watchdog
- Reinforced electromagnetic compatibility
Control and Communication Module: MAM
Monitoring of the rack
- Centralisation of alarms
- 3 relays available: Prealarm, Alarm, Defect
- Self-control of power supply lines
Communication
- 1 RS232 connection + 1 insulated RS485 connection
- Communication with MOVISET set-up software
- Communication with predictive maintenance software
- MODBUS communication with third system
4-channel protection module: MSVU
- Universal and fully parameterizable protection module
- Each channel can be configured separately
Inputs:
- 4 channels: ICP accelerometer or velocimeter or proximity probe with individual current limited transducer power supply
- 1 tacho/sync channel for proximity probe or TTL signal
- 2 dc 0/10V input channels devoted to the collection of measurement conditions
- 1 24Vdc logcal input for trip multiply
Outputs:
- 4 recorder dc outputs: 0-10V or 4-20 mA
- 4 bufferised ac outputs (terminal box on the rear panel)
- 4 bufferised ac outputs (BNC on the front panel)
- 4 relay command outputs
Calculation of monitoring indicators:
- Single or double integration
- Programmable filtering: band pass, narrow band, tracking filter
- Detection: RMS, peak or true or equivalent peak-to-peak
- Accelerometer-specific processing: 10-1000 Hz velocity according to ISO 2954, HF acceleration
- Proximity probe-specific processing: position (gap), pp vibration, Sppmax
Visual display on the front panel for each channel:
- OK light: status of transducer connection
- Pre-alarm light
- Alarm light
- By-pass light: Inhibited channel, manually or automatically if detected as defective
Alarms:
- 2 threshold levels per channel with validation delay
- Adjustable alarm logic: single-channel or dual-channel
- Command of relays in positive or negative logic, latching or non-latching.