4/20mA Displacement transmitter
WK systems are vibration or position transmitters using Eddy current probes.
The 4/20 mA interface makes long distance wiring possible. They are directly supplied by the current loop. It reduces installation cost.
Two transmitter types are available:
Vibration transmitter WK-142-K
- Relative vibration transmission
- Accuracy: ±1.5 % of full scale
- Available measurement ranges:
- 0 to 100 µ m pp
- 0 to 125 µ m pp
- 0 to 200 µ m pp
- 0 to 250 µ m pp
- 0 to 400 µ m pp
Position transmitter WK-142-T
- Relative position transmission
- Accuracy: ±1% of full scale
- Measurement range:
- -600 µ m to +600 µ m
- -25 mils to +25 mils
Other features
- Defect current: < 3.6 mA
- Conditions of defect: open circuit, short circuit, out of linear range
- Dynamic output for analysis
- Target material: JIS SCM440 (AISI 4140) ,plane
- Linear range*: 1.4 mm (Gap : 0.3 to 1.7mm)
- Sensitivity*: 7.87 mV/µm ± 6.5% typ. (interchangeability included)
- Frequency range* : 5 Hz to 6,000 Hz (+0 dB, -3 dB)
- Operating temperature ( transmitter): 0 to 70°C
- Operating temperature (probe & cables): -34 to +177°C
- Operating temperature (connectors): -34 to +125°C
- Humidity: 95% no condensation
- Power supply loop: 12 to 35 Vdc
- System length: 5 m or 7 m
- Dimensions of transmitter: (L) 100 mm × (l) 74 mm × (h) 50 mm
- Weight: 530g
*25°C, supply 24 Vdc flat target diam 30 mm in AISI 4140